AV Point Code Connection by BACnet IP #2379

Open
davidfungf opened this issue Feb 12, 2025 · 13 comments
Open

AV Point Code Connection by BACnet IP #2379

davidfungf opened this issue Feb 12, 2025 · 13 comments

Comments

@davidfungf
Copy link

When I configure the AV point code, it returned an error "Error(3011): Plugin tag not ready". AI point codes work fine. Something wrong of my AV point code configuration? Thanks.

BMS Source
Image

Neuron Screen Capture
Image

@ZhouBox
Copy link
Contributor

ZhouBox commented Feb 14, 2025

Which version of Neuron you are using?

@davidfungf
Copy link
Author

davidfungf commented Feb 14, 2025

I am using version 2.6.9

Image

@davidfungf
Copy link
Author

I upgraded it to version 3.3.0. Same result even though the device is connected. I used tcpdump -n udp port 47809 -X command to monitor the udp traffic. I uploaded the captured traffic file here for your analysis.

@ZhouBox
Copy link
Contributor

ZhouBox commented Feb 17, 2025

AI and AV on the same device?

@davidfungf
Copy link
Author

AI is belong to another sites. No BBMD device in the site. If we connect to the site via BBMD, does Neuron support it?

@ZhouBox
Copy link
Contributor

ZhouBox commented Feb 17, 2025

Image
Image

I analyzed your packet capture file and found that the packet was sent to BBMD. Since the neuron is a PTP packet, you can change the configured IP to the device's IP, such as 10.168.25.169, to see if the data can be read。

@davidfungf
Copy link
Author

Yes, I did. Here is another file. It connected to the device 10.168.25.169.

@ZhouBox
Copy link
Contributor

ZhouBox commented Feb 17, 2025

AI is belong to another sites. No BBMD device in the site. If we connect to the site via BBMD, does Neuron support it?

Based on the current actual test results, it appears that. Neuron no support via BBMD.

@davidfungf
Copy link
Author

I see. Thank you for your support!

@ZhouBox
Copy link
Contributor

ZhouBox commented Feb 17, 2025

@davidfungf 34 ping 169 is OK?

@ZhouBox
Copy link
Contributor

ZhouBox commented Feb 17, 2025

@davidfungf As far as I know, BBMD is a broadcast forwarding function between different subnets, and does not have a network routing function, or does it need to be configured with routing function.

@davidfungf
Copy link
Author

Currently, we are using enteliWeb to read the BMS devices. We want to replace it by Neuro but I don't know how enteliWeb do it.

Image

@ZhouBox
Copy link
Contributor

ZhouBox commented Feb 17, 2025

Thank you, I will study it.